|
|
Fire Marshal : F.F. Kyle Garon,
Assistant Deputy State Fire Marshal
Email: garon@ncfd.necoxmail.com
INSPECTION AND PLAN
REVIEW FEES
Every request for an inspection whether it
be Smoke/Carbon Monoxide or requests for plan or fire alarm system reviews are
completed under the provisions of the RI Fire Code:
All residential smoke and carbon
monoxide detector resale inspection, fee of $30.
-
New buildings, additions,
alterations, structures, etc. not covered by the above mentioned are subject
to the following fee figures based upon cost of construction:
Plan
Review Fee Schedule
New Buildings, Additions,
Alterations, etc (One Family Residential)
-
Valued at $ 500. or
Less Review Fee of $ 25.00
-
Valued over $ 500.00 but not over
$ 1000. Review Fee of $ 35.00
-
Valued over $1000.00 but not over
$ 2000. Review Fee of $ 45.00
-
Valued over $
2000. Review Fee of $ 60.00
Multi-family, Commercial,
Industrial, etc.
* (plus $1 per
thousand or fraction thereof over $ 2000)
* (plus $1 per thousand or
fraction thereof over $ 500,000)
SMOKE DETECTOR PLACEMENT
One, Two and Three Family Dwellings
- As of February 20, 2004 al new residential units
require hard-wired, interconnected smoke alarms with battery back up in the
following areas:
Outside each bedroom area and inside each bedroom
On each additional level including basements.
- In addition, interconnected heat detector(s) shall be
installed in al integral or attached garages in dwelling units permitted or
constructed after February 20, 2004.
- Wireless detectors shall be allowed provided that they
are monitored by an approved system or panel and provided that such system
meets all the audible requirements.
- While not required, it is highly recommended to place
an additional smoke alarm at the top of the basement stairs.
- Existing construction permitted after June 1976 are
required to maintain the previously required smoke alarms and they should be
hardwired and interconnected. These detectors shall be located outside
the bedroom areas and on each level.
- If the above units do not have the previously required
hard-wired systems they shall be allowed to have battery operated alarms.
Battery operated alarms shall not replace hard-wired alarms.
- Three family dwellings shall have hardwired,
interconnected smoke alarms installed by July 1, 2008. Interconnected in
common areas, separate from within each separate dwelling unit. (Also
hard-wired)
- All other existing construction shall require smoke
alarms outside each bedroom area and on each level. These will be permitted to
be battery operated.
One, Two, and Three Family
Dwellings Carbon Monoxide (CO) Detectors
- All new residential (including apartments and
condominiums) require hard-wired, interconnected CO alarms with battery back
up outside the bedroom areas.
- In addition, the local authority having jurisdiction
may require additional smoke or CO coverage in rooms or living areas having
pull out sofas or other means of sleeping arrangements if in his/her judgement
the room may be used for sleeping quarters on a regular or intermittent basis.
- Any dwelling permitted after January 1, 2002 shall be
required to have hardwired CO alarms with battery backup.
- All other existing construction shall be allowed to
have battery operated CO alarms or plug in units. Plug in units must be
restrained.
- Exception: Dwellings that do not contain any fuel
buring appliances, a fireplace or an attached or integrated garage are exempt
from CO requirements. If any of these items are introduced later, then
detection is required.
State Fire Marshal's Web Site:
http://www.fire-marshal.ri.gov
Fire Safety Code Web Site:
http://www.fsc.ri.gov
References; Rhode Island Uniform Fire Code 1 2003 Edition; Rhode Island
Life Safety Code 101 2003 Edition; NFPA 72 2002 Edition; NFPA 720 2003 Edition.
Placement of Smoke and CO
Alarms
- Ceiling mounted: At least 4 inches from any adjoining
wall surface
- Wall mounted: Between 4 and 12 inches from the ceiling
- Peaked or sloped ceilings: Within 36 inches or the peak
or high side of the slope, but no closer than 4 inches vertically or from an
adjoining wall surface.
- Detectors shall not be installed within 36 inches of
heating or cooling register, the tip of a ceiling paddle fan, a kitchen door
or a bathroom door containing a tub or shower.
- Detectors within a 20 foot horizontal path of a cooking
appliance shall be equipped with an alarm-silencing means or be of the photo
electric type.
- Where stairs lead to other occupied levels, a smoke
alarm or smoke detector shall be located so that smoke rising in the stairway
cannot be prevented from reaching the smoke alarm or smoke detector by an
intervening door or obstruction.
- For stairways leading up from a basement, smoke alarms
or smoke detectors shall be located on the basement ceiling near the entry to
the stairs.
- Near the first bedroom door in a hallway closet to the
living area
- Carbon Monoxide detectors shall be installed as per
manufacturer's recommendations outside each sleeping area.
Apartments/Townhouses/Condominiums
- Each dwelling unit shall comply with all of the
requirements of one and two family dwellings for smoke and carbon monoxide
alarms.
- In addition, every building meeting this definition
having between four and seven units shall be required to have a local fire
alarm system that will include detection in all common areas, pull stations,
etc; and occupant notification.
- Every building meeting this definition having more than
seven units shall be required to have a municipally connected fire alarm
system.
Exception:
-
Buildings that have units with suitable
fire resistance separation may be exempt from fire alarm system requirements.
-
Buildings that have central heating plants
that do not transfer heat via ductwork, and that have suitable separation from
the rest of the building, and where dwelling units do not have any other fuel
burning appliances, fireplaces or attached or integral garages, then they may
be exempt from CO requirements.
Contact your local Fire Marshal for Compliance
Information
Other Facts and
Responsibilities
- All detectors and devices shall be installed according
to manufacturer's recommendations.
- Smoke alarms shall not remain in service longer than 10
years from the date of installation unless otherwise specified by the
manufacturer.
- It shall be the responsibility of the owner to maintain
in operable condition smoke and carbon monoxide detection systems, installed
as required pursuant to this chapter, and the owner shall make operable within
seven (7) days after being notified by certified mail by the occupant and/or
enforcement official, any inoperable system.
- The cost of inspection ($30.00) shall be borne by the
seller.
- Owners of existing residential properties, previously
required to install smoke detectors, shall maintain those detectors in good
operating condition.
- The above smoke and carbon monoxide detectors may be
installed as either separate or combination units approved by the AHJ.
- The fire department for the community in which the
dwelling is located should inspect the smoke and carbon monoxide detector
systems of the dwelling within ten (10) days of a request from the owner.
- Once received smoke alarm and CO certificates are good
for 60 days
- It is recommended that you have your inspection
scheduled at least 2 weeks before your closing to allow time for any necessary
corrections.
Back to the top
|